Technical data | KL3214 |
---|---|
Number of inputs | 4 |
Power supply | via the K-bus |
Input filter limit frequency | typ. 1 kHz |
Sensor types | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, potentiometer: 10 Ω…1.2/4 kΩ, KTY sensors (types see documentation) |
Connection method | 3-wire |
Measuring range | -200…+850 °C (Pt sensors); -60…+250 °C (Ni sensors) |
Conversion time | approx. 170 ms default setting |
Measuring current | < 0.5 mA (load-dependent) |
Resolution | 0.1 °C per digit |
Measurement error/ uncertainty | < ±0.5 °C for Pt sensors |
Electrical isolation | 500 V (K-bus/signal voltage) |
Current consumption power contacts | – |
Current consumption K-bus | typ. 120 mA |
Special features | open-circuit recognition |
Weight | approx. 60 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE, UL |
Housing data | HD housing |
---|---|
Design form | HD (High Density) housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | – |
Wiring | solid conductors (e): direct plug-in technique; fine-stranded conductors (f) and ferrule (a): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…1.5 mm?, st*: 0.25…1.5 mm?, f*: 0.14…0.75 mm? |
Stripping length | 8…9 mm |