倍加福齐纳式安全栅模块
安全栅是倍加福的核心产品。我们提供全系列的产品用于保护危险区中的电信号。本质安全模块主要由限能齐纳栅和电气隔离组成。倍加福公司产品满足各种应用,适合多种安装。
Zener Barriers – Cost Saving and Easy Mounting Ex-Protection
Zener barriers provide cost saving Ex-protection for various applications in process automation systems. The amount of energy transferred to the hazardous location is limited to a safe level incapable of igniting the explosive atmosphere.
Z-system zener barriers from Pepperl+Fuchs are directly mounted on a 35 mm DIN-Rail. Through accessories, the required grounding can be done directly on the DIN mounting rail.
- Fast mounting on the DIN-rail
- Grounding directly connected with DIN-rail
- Separation of field loop by removing the fus
Z-system zener barriers are available with high density up to 2 channels / 12,5 mm width. Variants with field replaceable fuses provide a convenient means of disconnecting or open-circuiting the instrument loop without interfering with the wiring, making commissioning and maintenance operations much easier.
General specifications
Z828.H.F相关技术参数:
General specifications
Type
DC version, negative polarity
Electrical specifications
Nominal resistance
240 Ω
Series resistance
max. 273 Ω
Fuse rating
50 mA
Hazardous area connection
Connection
terminals 1, 2
Safe area connection
Connection
terminals 7, 8
Working voltage
max. 27 V , 26.5 V at 10 ?A
Conformity
Degree of protection
IEC 60529
Ambient conditions
Ambient temperature
-20 ... 60 °C (-4 ... 140 °F)
Storage temperature
-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Degree of protection
IP20
Connection
screw terminals , max. core cross-section 2 x 2.5 mm2
Mass
approx. 150 g
Dimensions
12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch)
Mounting
on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EC-Type Examination Certificate
BAS 00 ATEX 7096 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection
II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb≤ 60 °C) [circuit(s) in zone 0/1/2]
Statement of conformity
T?V 99 ATEX 1484 X , observe statement of conformity
Group, category, type of protection, temperature class
II 3G Ex nA II T4 [device in zone 2]
Directive conformity
Directive 94/9/EC
EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010
International approvals
FM approval
Control drawing
116-0118
UL approval
Control drawing
116-0355 (cULus)
CSA approval
Control drawing
116-0119
倍加福齐纳式安全栅模块产品型号参考:
Z705Z779.FZ887Z966.F
Z710Z779.HZ888Z966.H
Z713Z779.H.FZ896Z967
Z715.FZ786Z905Z978
Z722Z787Z910Z040
Z728Z787.FZ915Z041
Z728.CLZ787.HZ915.1KZ042
Z728.FZ787.H.FZ928Z810.CL
Z728.HZ788Z954Z813
Z728.H.FZ788.HZ955Z857
Z731Z788.RZ960Z864
Z755Z789Z960.FZ865
Z757Z796Z961Z865.F
Z764Z810Z961.FZ872
Z765Z822Z961.HZ879.F
Z765.FZ828.H.FZ964Z879.H.F
Z772Z878Z965Z886
Z778Z888.HZ966Z887.F
Z887.H.FZ922Z715.1KZ715
Zener barriers provide cost saving Ex-protection for various applications in process automation systems. The amount of energy transferred to the hazardous location is limited to a safe level incapable of igniting the explosive atmosphere.
Z-system zener barriers from Pepperl+Fuchs are directly mounted on a 35 mm DIN-Rail. Through accessories, the required grounding can be done directly on the DIN mounting rail.
- Fast mounting on the DIN-rail
- Grounding directly connected with DIN-rail
- Separation of field loop by removing the fus
Z-system zener barriers are available with high density up to 2 channels / 12,5 mm width. Variants with field replaceable fuses provide a convenient means of disconnecting or open-circuiting the instrument loop without interfering with the wiring, making commissioning and maintenance operations much easier.
General specifications
Z828.H.F相关技术参数:
General specifications | ||
Type | DC version, negative polarity | |
Electrical specifications | ||
Nominal resistance | 240 Ω | |
Series resistance | max. 273 Ω | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | max. 27 V , 26.5 V at 10 ?A | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals , max. core cross-section 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | BAS 00 ATEX 7096 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb≤ 60 °C) [circuit(s) in zone 0/1/2] | |
Statement of conformity | T?V 99 ATEX 1484 X , observe statement of conformity | |
Group, category, type of protection, temperature class | II 3G Ex nA II T4 [device in zone 2] | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0355 (cULus) | |
CSA approval | ||
Control drawing | 116-0119 |